25
XWEB5000
E
6-0005BEWX 0 00 E
SYSTEMS
0 = No
1 = Yes
Internal modem
HOW TO ORDER
RS485 socket
Alarm 1 output relay Printer connection
System alarm relay Digital input
RJ45 Ethernet connector
Internal modem line connector
External modem socket
Monitor connection
Keyboard/mouse socket
USB socket for connection of device
Alarm 2 output relay
1,3GHz CPU
512MB internal memory
120GB HD
1 LAN output
2 USB outputs
110/230Vac ±10% power supply
1 RS485 serial line for device (ModBUS – RTU) connection
1 RS232 output for external modem connection
1 system alarm relay output
2 RS485 alarm relay outputs
1 print output (25 pin)
1 digital input
1 keyboard/mouse connector
1 video output
Sampling time programmable from 1 to 255 minutes
Analogue internal modem (optional)
With XWEB5000 it’s possible to intervene sending commands to
monitored devices. The installer can create a supervision “Project” (or
several “Projects”) by programming links between the input variables
(inputs, status and outputs of a controller) and defining what actions the
system must take when these conditions are met. Unlike a standard PLC,
where the user is required to know a specific programming language,
with the XWEB5000 the “project” can be easily created using a simple
graphic user interface, but importantly, without the need to learn a
complex programming language. A specific software is not necessary:
the supervising software has been written in JAVA and it runs on the
client PC. The project is saved to the XWEB5000; several project can be
run simultaneously.
SUPERVISING
More information about functions and connections at pages 26÷30