1592017410 XLH360 GB r1.0 15.04.2005.doc XLH360 16/16
Label Value Menu Description Range
dot
20 Pr2 Delay of temperature alarm after closing the door 0 ÷ 250 min
AHc
Ab Pr2 Humidity alarm configuration rE = relative / Ab = absolute
AHL
0.0 Pr1 Low humidity alarm setting 0 ÷ 50 / Lci ÷ AHu
AHu
100 Pr1 High humidity alarm setting 0 ÷ 50 / AHL ÷ uci
AHH
2.0 Pr2 Humidity alarm recovery differential 0.5 ÷ 25
AHd
15 Pr2 Humidity alarm delay 0 ÷ 250 min
dHo
1.3 Pr2 Delay of humidity alarm at start-up 0.0 ÷ 23.5 h
doH
20 Pr2 Alarm delay at the end of defrost 0 ÷ 250 min
doA
20 Pr2 Open door alarm delay 0 ÷ 250 min ( 250 = nu )
tbA
oFF Pr2 Relay status after pushing a key on÷oFF
nPS
15 Pr2 Pressure switch number 0÷15
ot
0.0 Pr1 Thermostat probe calibration -12.0 ÷ 12.0
oE
0.0 Pr2 Evaporator probe calibration -12.0 ÷ 12.0
o3
0.0 Pr1 Humidity probe calibration -10 ÷ 10
P2P
YES Pr2 Evaporator probe presence no = absent / YES = present
P3P
YES Pr2 Humidity probe presence no = absent / YES = present
Lci
0.0 Pr2 Readout with 4 mA -999 ÷ 999
uci
100 Pr2 Readout with 20 mA -999 ÷ 999
i1P
cL Pr2 Configurable digital input polarity cL =open / oP = close
i2P
cL Pr2 Door switch digital input polarity cL =open / oP = close
i1F
dor Pr2 Digital input configuration dor / PAL / EAL / bAL / Ht
odc
FAn Pr2 Outputs status when open door on / Fan / oFF
rrd
YES Pr2 Outputs restarting after doA alarm no = no / YES = yes
did
0 Pr2 Digital input alarm delay 0÷255 min.
oA1 LiG Pr2 Light relay configuration 1
ALr = alarm; dEH = dehumidifier; onF =
on/off; Lig = light, ESt, dEF not select
oA2 ESt Pr2 Light relay configuration 2
ALr = alarm; dEH = not use; onF = on/off;
Lig = light, ESt= extractor, dEF =defrost
Adt
1 Pr2
Serial address for temperature 0÷247 num
AdH
1 Pr2
Serial address for humidity 0÷247 num
Ptb
- - - Pr2 Parameter table - - -
rEL
- - - Pr2 Software release - - -
Prd
- - - Pr2 Probes display Pb1÷Pb3
Pr2
- - - Pr1 Access to the protected parameter list - - -